Parameters

Digital Inputs

Access
PNU
ID
RUN
P3.1
300
P3.2
403
P3.3
404
P3.4
412
P3.5
405
72
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Value/Range
Description
Start/Stop-Logic
0
P3.2 (FWD), P3.3 (REV), REAF
REAF (Restart after Fault) = Restart after an error message
Function same as P3.1 = 3
The automatic restart after an error message (FAULT) requires
setting P6.13 = 1
The rising edge of the control voltage at control signal terminal
8 (P3.2) or control signal terminal 9 (P3.3) is then not controlled
1
P3.2 (FWD) + P3.3 = REV (see Example A on Page 76)
2
P3.2 (Start pulse), P3.3 (Stop pulse)
Start and stop command via the control signal (P3.2 = Start)
(P3.3 = Stop) by a momentary pulse (+24V)
(see Example B on Page 76)
3
P3.2 (FWD), P3.3 (REV)
P3.2 (control signal terminal 8) starts the drive with a clockwise
rotating field (FWD) and P3.3 (control signal terminal 9) with an
anticlockwise rotating field (REV). Both control commands are
interlocked (exclusive OR)
Start signal/Start FWD (1)
0
Deactivated
1
Activated via control signal terminal 8 (DI1)
2
Activated via control signal terminal 9 (DI2)
3
Activated via control signal terminal 10 (DI3)
4
Activated via control signal terminal 14 (DI4)
5
Activated via control signal terminal 15 (DI5)
6
Activated via control signal terminal 16 (DI6)
STOP signal/Start REV(1)
Like P3.2
Allocation of the function to control signal terminals
Reverse (changes the direction of the field of rotation from
FWD to REV)
Like P3.2
Allocation of the function to control signal terminals
Ext. fault close (N/O)
Like 3.2
Allocation of the function to control signal terminals
Error message when applying +24V to the assigned control
signal terminal (DI1 to DI6)
Factory Setting
(P1.3)
3
1
2
0
0