Pid Controller - Eaton M-Max Series User Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

PID Controller (P9)
The M-Max series frequency inverters are provided with a
PID controller that you activate with P9.1 = 1. The controller
can be deactivated via a digital input (P3.12).
PID control is superimposed on the frequency inverter
function. You should therefore set all of the frequency
inverter's drive-related parameters, such as maximum output
frequency (motor speed), acceleration and deceleration
ramps (mechanical load, belts). Frequency inverter and motor
are process-integrated actuators. The output frequency to
the motor (which determines the speed) is specified as
manipulated variable from the PID controller.

PID Controller

Access
PNU
ID
RUN
P9.1
163
P9.2
118
P9.3
119
P9.4
167
P9.5
332
Value/Range
Description
PID Controller
0
Deactivated
1
Activated for drive control
2
Activated for external application
PID controllers, P gain
0–1000%
Proportional Gain (KP)
Low values attenuate the control action
High values can cause oscillation
PID controller, I reset time
0–320s
Integral time constant
PID controller setpoint, keypad reference
0–100%
Setpoint setting range utilizing keypad as reference P9.5 = 0
PID controller, setpoint source
The setting range is limited by P6.3 (raised starting frequency)
and P6.4 (end frequency)
0
Keypad (P9.4)
1
Fieldbus
2
AI1
3
AI2
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
When the PID controller is activated, the setpoints and actual
values become process variables and are normalized
automatically into percentages (%). For example, the
specified setpoint (0–100%) here is the same as a volume
3
flow (0–50 m
/h). The actual value here is the volume flow
3
(m
/h) from a suitable sensor, which is evaluated again as a
percentage (0–100%).
If this process data is to be displayed in the physical variable
3
(m
/h), you can set the conversion with parameter P9.19
(see "Display factor (P9.19)").
Parameters
Factory Setting
(P1.3)
0
100
10.0
0.0
0
95

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents