V/Hz-Characteristic Curve (P11.1) - Eaton M-Max Series User Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

Parameters

V/Hz-Characteristic Curve (P11.1)

V
(%)
P11.3
P11.6
P6.3
P11.2
Characteristic Curve: V/Hz (P11.1) Linear
P11.1 = 0
V/Hz-Characteristic Curve, continued
Access
PNU
ID
RUN
P11.2
602
X
P11.3
603
X
108
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
V
(%)
P11.3
P11.6
Hz
P6.3
Value/Range
Description
Cut-off frequency
30–320 Hz
The output voltage reaches its maximum rated value P11.3 with
the cut-off frequency. For example: 400V at 50 Hz
If the maximum output frequency (P6.4) is set to higher values,
the output voltage remains constant as of the cut-off frequency
defined here
As of this cut-off frequency, the voltage/frequency ratio is no
longer constant. The magnetization of the connected motor is
reduced with increasing frequency (field weakening range)
Example: Linear V/Hz Characteristic Curve with Cut-Off
Frequency and Field Weakening Range
V
(%)
P11.3
P11.6
P6.3
Output voltage
10–200%
Input voltage
In the standard application, the value set here is equal to 100%
of the input voltage supply and corresponding with the nominal
motor voltage set under P7.5 (see the motor ratings plate)
Hz
P11.2
Squared
P11.1 = 1
P11.2
V
(%)
P11.3
P11.5
P11.6
P11.4
P11.2
Configurable
P11.1 = 2
Factory Setting
(P1.3)
60.00
Hz
P6.4
100.00
Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents