Installation
Analog Outputs
The frequency inverter provides an analog voltage signal
(0–10V) at control signal terminal 18. This signal is factory set
proportional to the output frequency (0–f max ). The calibration
and parameterization of the analog output are described in
"Analog Outputs (P4)" on Page 77.

Analog Output AO (Connection Examples)

5
18
+
Digital Inputs
The frequency inverter has six digital inputs (DI1 to DI6) that
have an identical function and operation. Their actuation is
factory set for +24V (positive logic, source type). You can use
the device internal control voltage of control signal terminal 6
(+24V, maximal 50 mA) or an external voltage source (+24V)
with a residual ripple less than ±5%
parameterizable functions are described in "Digital Inputs
(P3)" on Page 71.

Digital Inputs with Internal Supply Voltage

6
7
8
S1
S1 = LOGIC+
(Source Type)
42
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
U a /U a . The
9

Digital Inputs with External Supply Voltage

+ 24V
0V
U
a
(
)
±5%
U
a
6
7
8
S1
S1 = LOGIC+
(Source Type)
The factory set functions and the electrical connection data
are shown in "Control Signal Terminal Functions" on
Page 40.
Microswitch S1 (LOGIC) is used to change the control logic
to so-called negative logic (sink type). The digital inputs are
connected internally or externally via control signal terminal 7
(DI_COM) directly to +24V and to the corresponding 0V
potential (GND) via input terminals DI1 to DI6.
Digital Inputs with Internal Supply Voltage
(Negative Logic, Sink Type)
6
7
8
S1
S1 = LOGIC–
(Sink Type)
9
9
5