Parameter Selection; Analog Input - Eaton M-Max Series User Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

Appendix A
All Parameters
When first switching on or after activating the default settings (S4.2 = 1) parameter P1.1 must
be set to 0 for access to all parameters.

Parameter Selection

Access
PNU
ID
RUN
P1.1
115
P1.2
540
X
P1.3
1472
X

Analog Input

Access
PNU
ID
RUN
P2.1
379
P2.2
380
P2.3
381
P2.4
378
P2.5
390
P2.6
391
P2.7
392
P2.8
389
164
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
ro/rw
Designation
rw
Quick start parameters
rw
Application
rw
Country specific default settings
ro/rw
Designation
rw
AI1 signal range (analog input)
rw
AI1 custom minimum
rw
AI1 custom maximum
rw
AI1, filter time
rw
AI2 signal range (analog input)
rw
AI2 custom minimum
rw
AI2 custom maximum
rw
AI2, filter time
Value Range
0 = All parameters
1 = Only quick configuration
parameters
0 = Basic
1 = Pump drive
2 = Fan drive
3 = High load
0 = EU
1 = USA
Value Range
(microswitch S2)
0 = 0–10V/0–20 mA
1 = 2–10V/4–20 mA
–100.00 to 100.00%
–100.00 to 100.00%
0.0–10.0s
(microswitch S3)
Like P2.1
–100.00 to 100.00%
–100.00 to 100.00%
0.0–10.0s
FS
User
Page
(P1.3)
Setting
66/67
1
67
0
67
1
FS
User
Page
(P1.3)
Setting
68
0
68
0
68
100
68
0.1
69
1
69
0
69
100
69
0.1