List of Parameters

The abbreviations used in the parameter lists have the
following meaning:
PNU
Parameter number
ID
Identification number of the parameter
RUN
Access to the parameters during operation (RUN):
= Modification permissible,
X = Modification only possible in STOP
ro/rw
Parameter read and write permissions via a fieldbus
connection (BUS):
ro = read only
rw = read and write
FS
Factory setting of the parameters
User setting
User setting of the parameters
Quick Start Parameter Guide (Full parameter guide begins on Page 164)
Access
PNU
ID
RUN
P1.1
115
P1.2
540
X
P1.3
1472
X
P6.1
125
P6.2
117
P6.3
101
X
P6.4
102
X
P6.5
103
X
P6.6
104
X
P6.7
505
X
P6.8
506
X
ro/rw
Designation
rw
Quick start parameters
rw
Application
rw
Country specific default
settings
rw
Primary remote control source
rw
Primary remote speed reference
rw
Minimum frequency
rw
Maximum frequency
rw
Primary acceleration time (acc1)
rw
Primary deceleration time (dec1)
rw
Start function
rw
Stop function
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Quick Configuration (Basis)
When first switching on or after activating the default
settings (S4.2 = 1), you are guided step by step through the
provided parameters by the quick start assistant. The defined
values are confirmed with the OK button or they can be
changed to suit your application and the motor data.
The quick start assistant can be switched off in the first
parameter (P1.1) by entering a zero (access to all
parameters).
In parameter P1.2, you can switch to the specified
application setting with the quick start assistant (see table on
Page 40).
The quick start assistant ends this first cycle by automatically
switching to frequency display (M1.1 = 0.00 Hz).
By selecting the parameter level (PAR) again, besides the
selected parameters for the quick configuration, the system
parameters (S) are also shown in other cycles.
Value Range
0 = All parameters (disable)
1 = Only quick configuration parameters
(enable)
0 = Basic
1 = Pump drive
2 = Fan drive
3 = High load
0 = EU
1 = NA
1 = Control signal terminals (I/O)
2 = Control unit (KEYPAD)
3 = Fieldbus (BUS)
0 = Fixed frequency (FF0)
1 = Control unit (KEYPAD)
2 = Fieldbus (BUS)
3 = AI1 (analog setpoint 1)
4 = AI2 (analog setpoint 2)
5 = Motor potentiometer
0.00–P6.4 Hz
P6.3–320.00 Hz
0.1–3000s
0.1–3000s
0 = Acceleration time (ramp)
1 = Flying restart circuit
0 = Fee coasting
1 = Deceleration time (ramp)
Appendix A
FS
User
Page
(P1.3)
Setting
67
1
67
0
67
1
82
0
82
3
83
0.00
83
60.00
83
3.0
83
3.0
84
0
84
0
161