Logic Function

Access
PNU
ID
RUN
P13.1
1453
X
Value/Range
Description
LOG function, Selection input A
Value range for signal A
0
Deactivated
1
READY, the frequency inverter is ready for operation
2
RUN, the inverter of the frequency inverter is enabled
(FWD, REV)
3
FAULT, error message
Error detected (= STOP)
4
Error message inverted (no error message)
5
ALARM, warning message
(see "Protective Functions (P8)" on Page 90)
6
REV (Reverse run), anticlockwise rotating field active
7
Output frequency = frequency setpoint
8
Motor controller active
9
Zero frequency
Output frequency = 0 (Hz)
10
Frequency monitoring 1
For the frequency ranges set at P5.4 and P5.5
11
Frequency monitoring 2
For the frequency ranges set at P5.6 and P5.7
12
PID monitoring
For the deviation set at P9.17
13
Overtemperature signal
14
Overcurrent control active
15
Overvoltage control active
16
PLC Sequence control active
17
PLC Sequence control, single step completed
18
PLC Sequence control, program cycle completed
19
PLC Sequence control, pause
20
Counter, value 1 reached
The counter value is
can be reset by activating P3.24
21
Counter, value 2 reached
The counter value is
can be reset by activating P3.24
22
RUN message active
23
Analog minimum reference error
Message, AL 50 if the value of AI1 and/or AI2 goes below
the 4 mA or 2V setpoint value (live zero) (P2.1 = 1, P2.5 = 1)
Values continued on next page
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
the trigger value set at P3.21 and
the trigger value set at P3.22 and
Parameters
Factory Setting
(P1.3)
0
119