Settings Menu

The inverter system allows some parameters to be set from the front panel.
Press
1
A 4-digit numeric password is requested.
2
Password:
* * * *
The Settings section is divided into two categories:
Inverter - parameters related to the inverter functions
System - system related setups.

Inverter Parameter Settings

Parameter
Output volt
Output Freq
OPV HL: High loss of
inverter output voltage
OPV LL: Low loss of
inverter output voltage
IPV LVSD
IPV HVSD
Power Limited
Inverter On/Off
AC HL: High loss of AC
input
AC LL: Low loss of AC
input
12
then
to select Settings.
Press
decrease the number. Then press
Setting Option
Inverter output voltage
For 230Vac output:
1) 208 Vac; 2) 220 Vac; 3) 230 Vac; 4) 240 Vac
For 110Vac output:
1) 110Vac; 2) 115Vac; 3)120Vac
Inverter output frequency: 50Hz or 60Hz
For Output volt = 230V, adjustable 220 - 276V
For Output volt = 110V, adjustable 117 - 138V
For Output volt = 230V, adjustable 176 - 230V
For Output volt = 110V, adjustable 90 - 115V
The minimum input voltage for inverter normal operation:
Adjustable 40 - 44V.
The maximum input voltage for inverter normal operation:
Adjustable 59 - 61V.
Inverter output power capacity:
Adjustable 50 - 100%.
Turns the inverter output ON/OFF. The controller and the
static switch remain operational.
For Output volt = 230V, adjustable 220 - 276V
For Output volt = 110V, adjustable 117 - 138V
For Output volt = 230V, adjustable 176 - 230V
For Output volt = 110V, adjustable 90 - 115V
Copyright © 2017 Eaton Corporation. All Rights Reserved.
IPN 997-00012-72C
to select the first digit. Press
The initial password is 0000. No setting modification can be
executed if a wrong password is entered.