Drive parameter backup mode
Parameter backup mode is used to export parameters from one
drive to another or to make a backup of the drive parameters.
Uploading to panel stores all parameters, including two user sets
and an override set, to the drive control panel (operator keypad).
The full set, partial parameter set (application), user sets and
override set can then be downloaded from the control panel to
another drive or the same drive.
The control panel memory is non-volatile and does not depend
on the panel battery.
Depending on the motor and application, the following options
are available in the Drive parameter backup mode:
UPLOAD TO PANEL – Copies all parameters from the drive
to the control panel. This includes all defined user parameter
sets, override parameter set and internal (not adjustable by
the user) parameters such as those created by the ID Run).
BACKUP INFO – Shows the following information about the
drive whose parameters have been uploaded to the panel:
drive type, drive rating and FW (firmware) version.
DOWNLOAD FULL SET – Restores the full parameter set
from the control panel to the drive. This writes all parameters,
including the internal non-user-adjustable motor parameters,
to the drive. It does not include the user parameter sets or the
override parameter set.
Note: Use the Download full set function only to restore a drive
from a backup if something has gone wrong or to transfer
parameters to systems that are identical to the original system.
DOWNLOAD APPLICATION – Copies a partial parameter
set (part of the full set) from the control panel to the drive.
The partial set does not include user sets, override set,
internal motor parameters, parameters 9905...9909, 1605,
1607, 5201, nor any
Group 53: EFB PROTOCOL
This is recommended when using the same application for
drives of different sizes.
DOWNLOAD USER SET 1 – Copies the parameters in user
set 1 from the control panel to the drive. A user set includes
Group 99: START-UP DATA
motor parameters.
74
ACH550 User's Manual
Group 51: EXT COMM MODULE
parameters.
parameters and the internal
Start-up and control panel
and