Code Description
1202 CONST SPEED 1
Sets value for constant speed 1.
• The range and units depend on parameter 9904
• Range: 0...30000 rpm when 9904 = 1 (
• Range: 0...500 Hz when 9904 = 3 (
1203
CONST SPEED 2...CONST SPEED 7
...
1208
Each sets a value for a constant speed.
• See
CONST SPEED
1209 TIMED MODE SEL
Defines timer-activated constant speed mode. Timer can be used to
change between the external reference and a maximum of three
constant speeds or to change between a maximum of 4 selectable
speeds, i.e. constant speeds 1, 2, 3 and 4.
1 =
/
EXT
CS
selects constant speed 1 when only timer 1 is active, selects constant
speed 2 when only timer 2 is active and selects constant speed 3
when both timers 1 and 2 are active.
1
TIMER
0
1
0
1
2 =
1/2/3/4 – Selects constant speed 1 when no timer is active,
CS
selects constant speed 2 when only timer 1 is active, selects constant
speed 3 when only timer 2 is active, selects constant speed 4 when
both timers are active.
1
TIMER
0
1
0
1
194
1 above.
1/2/3 – Selects an external speed when no timer is active,
2 Function
TIMER
0
External reference
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
1
Constant speed 3 (1204)
2 Function
TIMER
0
Constant speed 1 (1202)
0
Constant speed 2 (1203)
1
Constant speed 3 (1204)
1
Constant speed 4 (1205)
ACH550 User's Manual
Range
0...30000 rpm /
0...500 Hz
MOTOR CTRL MODE
:
VECTOR
SPEED
:
SCALAR
FREQ
0...30000 rpm /
0...500 Hz
1...2
Parameter listing and descriptions
).
).
: