ABB ACH550-01 User Manual page 400

0.75...110 kw/1...150 hp
Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Hardware description
X1
1
SCR
2
AI1
3
AGND
4
+10 V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
388
Hardware description
Terminal for signal cable screen (connected internally to
chassis ground).
Analog input channel 1, programmable.
2
Default
= frequency reference. Resolution 0.1%,
accuracy ±1%.
Two different DIP switch types can be used.
J1: AI1 OFF: 0...10 V (R
J1: AI1 ON: 0...20 mA (R
Analog input circuit common (connected internally to the
chassis ground through 1 Mohm).
10 V/10 mA reference voltage output for analog input
potentiometer (1...10 kohm), accuracy ±2%.
Analog input channel 2, programmable. Default
used. Resolution 0.1%, accuracy ±1%.
Two different DIP switch types can be used.
J1: AI2 OFF: 0...10 V (R
J1: AI2 ON: 0...20 mA (R
Analog input circuit common (connected internally to the
chassis ground through 1 Mohm).
Analog output, programmable. Default
0...20 mA (load < 500 ohm)
Analog output, programmable. Default
0...20 mA (load < 500 ohm)
Analog output circuit common (connected internally to
the chassis ground through 1 Mohm).
ACH550 User's Manual
= 312 kohm)
i
= 100 ohm)
i
= 312 kohm)
i
= 100 ohm)
i
2
= frequency.
2
= current.
Technical data
2
= not

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-uh

Table of Contents