Status Word. The Status Word is a 16-bit word containing status
information, sent by the drive to the fieldbus controller. The
following table and the state diagram on page
Status Word content.
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STA
5
OFF_3_STA
6
SWO_ON_INHIB 1
7
ALARM
8
AT_SETPOINT
9
REMOTE
152
Status Word
Description (corresponds to states/boxes
Value
in the state diagram)
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
READY TO OPERATE
0
1
OFF
ACTIVE
1
OPERATION ENABLED
0
(
NOT READY
0...1
FAULT
0
No fault
1
2
OFF
INACTIVE
0
2
OFF
ACTIVE
1
3 inactive
OFF
0
3
OFF
ACTIVE
-
SWITCH
ON INHIBITED
0
1
Alarm is active.
0
No alarm
1
. Actual value equals reference
OPERATING
value (= is within tolerance limits).
0
Actual value differs from reference value (= is
outside tolerance limits).
1
Drive control location:
0
Drive control location:
ACH550 User's Manual
154
describe the
OPERATION INHIBITED
(
REMOTE
(
LOCAL
REM
Serial communications
)
)
AUTO
)