Code Description
5307 EFB CRC ERRORS
Contains a count of the messages with a CRC error received by the
drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate
errors.
• CRC calculations for possible errors.
5308 EFB UART ERRORS
Contains a count of the messages with a character error received by the
drive.
5309 EFB STATUS
Contains the status of the EFB protocol.
0 =
– EFB protocol is configured, but not receiving any messages.
IDLE
1 =
.
EXEC
INIT
2 =
TIME OUT
the network master and the EFB protocol.
3 =
CONFIG ERROR
4 =
-
OFF
LINE
addressed to this drive.
5 =
-
– EFB protocol is receiving messages that are addressed to
ON
LINE
this drive.
6 =
– EFB protocol is performing a hardware reset.
RESET
7 =
LISTEN ONLY
5310 EFB PAR 10
Specifies the parameter mapped to Modbus Register 40005.
5311 EFB PAR 11
Specifies the parameter mapped to Modbus Register 40006.
5312 EFB PAR 12
Specifies the parameter mapped to Modbus Register 40007.
5313 EFB PAR 13
Specifies the parameter mapped to Modbus Register 40008.
5314 EFB PAR 14
Specifies the parameter mapped to Modbus Register 40009.
5315 EFB PAR 15
Specifies the parameter mapped to Modbus Register 40010.
5316 EFB PAR 16
Specifies the parameter mapped to Modbus Register 40011.
5317 EFB PAR 17
Specifies the parameter mapped to Modbus Register 40012.
Parameter listing and descriptions
– EFB protocol is initializing.
– A time-out has occurred in the communication between
– EFB protocol has a configuration error.
– EFB protocol is receiving messages that are NOT
– EFB protocol is in listen-only mode.
Range
0...65535
0...65535
0...7
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535