Ratings, 208...240 volt drives
IEC ratings
Type code
ACH550-01-
Three-phase supply voltage, 208...240 V
04A6-2
06A6-2
07A5-2
012A-2
017A-2
024A-2
031A-2
046A-2
059A-2
075A-2
088A-2
114A-2
143A-2
178A-2
221A-2
248A-2
I
: Maximum output current allowed for 2 seconds every minute
MAX
374
Valid up to 40°C
I
P
2N
N
A
kW
4.6
0.75
6.6
1.1
7.5
1.5
11.8
2.2
16.7
4.0
24.2
5.5
30.8
7.5
46.2
11.0
59.4
15.0
74.8
18.5
88.0
22.0
114
30.0
143
37.0
178
45.0
221
55.0
248
75.0
ACH550 User's Manual
Max. current I
MAX
A
6.3
8.3
11.9
13.5
21.2
30.1
43.6
55
83
107
135
158
205
270
320
346
00467918.xls A.7
Technical data
Frame
size
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R4
R4
R6
R6
R6
R6