ACH550 User's Manual
NEMA ratings
Type code
ACH550-UH-
Three-phase supply voltage, 208...240 V
04A6-2
06A6-2
07A5-2
012A-2
017A-2
024A-2
031A-2
046A-2
059A-2
075A-2
088A-2
114A-2
143A-2
178A-2
221A-2
248A-2
I
: Maximum output current allowed for 2 seconds every minute
MAX
Technical data
Valid up to 40°C
I
P
2N
N
A
HP
4.6
1.0
6.6
1.5
7.5
2.0
11.8
3.0
16.7
5.0
24.2
7.5
30.8
10.0
46.2
15.0
59.4
20.0
74.8
25.0
88.0
30.0
114
40.0
143
50.0
178
60.0
221
75.0
248
100
Max. current I
MAX
A
6.3
8.3
11.9
13.5
21.2
30.1
43.6
55
83
107
135
158
205
270
320
346
00467918.xls A.7
Frame
size
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R4
R4
R6
R6
R6
R6
375