ABB ACH550-01 User Manual page 276

0.75...110 kw/1...150 hp
Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Overview of PID controllers
PID controller – Basic set-up
In PID control mode, the drive compares a reference signal
(setpoint) to an actual signal (feedback), and automatically
adjusts the speed of the drive to match the two signals. The
difference between the two signals is the error value.
Typically PID control mode is used when the speed of a fan or
pump needs to be controlled based on pressure, flow or
temperature. In most cases – when there is only 1 transducer
signal wired to the ACH550 – only parameter
PROCESS PID SET 1
A schematic of setpoint/feedback signal flow using parameter
group 40 is presented on page 265.
264
is needed.
Parameter listing and descriptions
ACH550 User's Manual
Group 40:

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-uh

Table of Contents