ABB ACH550-01 User Manual page 60

0.75...110 kw/1...150 hp
Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

5.
Connect the input power, motor and the grounding wires to
the drive terminals. Frame size R6: See the figures below.
R6: Cable lug installation (16...70 mm
R6: Cable terminal installation (95...185 mm
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING! If the wire size is less than 95 mm
cable lug must be used. A cable of wire size less than 95
mm
may damage the drive.
Note: Check the cable lengths according to section
EMC considerations
48
2
(3/0 AWG) connected to this terminal will loosen and
on page 26.
ACH550 User's Manual
2
/ 6...2/0 AWG cables)
Remove the screw
terminals. Fasten cable
lugs to the remaining
bolts with M10 nuts.
Isolate the ends of the
cable lugs with insulating
tape or shrink tubing.
2
/ 3/0...350 AWG cables)
b
a
2
(3/0 AWG), a
Wiring and
Installing the drive

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-uh

Table of Contents