ACH550 User's Manual
Motor cable length
The table below shows the maximum motor cable lengths for
400 V drives with different switching frequencies. Examples for
using the table are also given.
Second environment
(category C3
Frame
size
1 kHz 4 kHz 8 kHz 1 kHz 4 kHz 8 kHz 1/4 kHz
R1
300
300
R2
300
300
R3
300
300
R4
300
300
R5
100
100
R6
100
100
1
See the new terms in section
2
12 kHz switching frequency is not available.
3
Not tested.
Sine filters further extend the cable lengths.
Under heading "Operational limits", the "Basic unit" columns
define the cable lengths with which the basic drive unit works
without problems within the drive specification, without installing
any further options. Column "With du/dt filters" defines the cable
lengths when an external du/dt filter is used.
The columns under heading "EMC limits" show the maximum
cable lengths with which the units have been tested for EMC
emissions. The factory guarantees that these cable lengths
meet the EMC standard requirements.
If external sine filters are installed, longer cable lengths can be
used. With sine filters the limiting factors are the voltage drop of
the cable, which has to be taken into account in engineering, as
well as the EMC limits (where applicable).
The default switching frequency is 4 kHz.
WARNING! Using a motor cable longer than specified in the
table above may cause permanent damage to the drive.
Technical data
Maximum cable lengths (400 V)
EMC limits
First environment
1
)
(category C2
300
300
300
300
300
100
300
300
75
300
300
75
100
100
100
3
100
100
IEC/EN 61800-3 (2004) Definitions
Operational limits
1
)
Basic unit
8/12
kHz
300
100
100
30
200
100
75
200
100
75
200
100
2
100
300
150
2
3
300
150
on page 413.
With
du/dt
filters
150
250
250
300
300
300
385