8. Internal timer
This application macro is for applications where the motor is
started and stopped with a built-in timer. This macro has also a
boost function which operates the motor after digital input 3
(DI3) has been momentarily activated. An example of the timer
usage is shown below. For further information see chapter
time clock and timed
When using a direct speed reference in the AUTO mode, the
speed reference must be connected to analog input 1 (AI1) and
the START command is given with digital input 1 (DI1). In the
HAND/OFF mode, the speed reference and START command
are given through the control panel (operator keypad).
If process PI(D) is used, the feedback signal must be connected
to analog input 2 (AI2). By default, the setpoint is set from the
control panel, but it can also be changed to analog input 1.
Process PI(D) must be commissioned and adjusted with
parameters
control assistant (recommended).
24:00
22:00
20:00
18:00
16:00
14:00
12:00
10:00
08:00
06:00
04:00
02:00
00:00
102
functions.
(Group 40: PROCESS PID SET
Time
Time period 2
period
1
Mon
Tue
Wed
ACH550 User's Manual
1) or using the PID
Time
period
3
Time
period
4
Thu
Fri
Sat
Sun
Application macros and wiring