NEMA ratings
Type code
ACH550-UH-
Three-phase supply voltage, 380...480 V
02A4-4
03A3-4
04A1-4
06A9-4
08A8-4
012A-4
015A-4
023A-4
031A-4
038A-4
044A-4
059A-4
072A-4
077A-4
096A-4
124A-4
157A-4
180A-4
I
: Maximum output current allowed for 2 seconds every minute
MAX
Technical data
Valid up to 40°C
I
P
2N
N
A
HP
2.4
1.0
3.3
1.5
4.1
2.0
6.9
3.0
8.8
5.0
11.9
7.5
15.4
10.0
23
15
31
20
38
25
44
30
59
40
72
50
77
60
96
75
124
100
157
125
180
150
Max. current I
MAX
A
3.1
4.3
5.9
9.7
12.4
15.8
21.4
27.7
41
56
68
79
106
117
139
173
223
281
00467918.xls A.7
Frame
size
R1
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R4
R4
R5
R5
R6
R6
R6
373