Suitable mounting location
Confirm that the mounting location meets the following
constraints:
The drive must be mounted vertically on a smooth,
non-flammable, solid surface, and in a suitable environment
as defined in section
page 22.
For horizontal installation, contact ABB for more information.
Mounting on a machine frame is also possible. No additional
plates are needed for cooling as the drive has an integral
heatsink backplate.
See section
dimensions for all frame sizes and protection types.
The figure below shows the necessary free space for the
installation of the unit.
IP21 & IP54: 0 mm [0 in]
Preparing for installation
Suitable environment and enclosure
Mounting dimensions
R1...R6
IP21 & IP54: 200 mm [8 in]
IP21 & IP54: 200 mm [8 in]
on page
394
for mounting
IP21 & IP54: 0 mm [0 in]
on
23