NEW PARAMETERS AND PARAMETER VALUES
This new group defines supervision of user adjustable load curves (motor torque as
a function of frequency). The curve is defined by five points. - The function replaces
deleted underload parameters 3013...3015.
Code Description
3701 USER LOAD C MODE
Supervision mode for the user adjustable load
curves. This functionality replaces the former
underload supervision in Group 30: FAULT
FUNCTIONS.
0 =
– Supervision is not active.
NOT SEL
1 =
– Supervision for the torque
UNDERLOAD
dropping below the underload curve.
2 =
– Supervision for the torque
OVERLOAD
exceeding the overload curve.
3 =
– Supervision for the torque dropping
BOTH
below the underload curve or exceeding the
overload curve.
3702 USER LOAD C FUNC
Action wanted during load supervision.
1 =
– A fault is generated when the condition defined by 3701
FAULT
the time set by 3703
2 =
– An alarm is generated when the condition defined by 3701
ALARM
half of the time defined by 3703
Language
English
EN
Danish
DA
German
DE
Spanish
ES
Finnish
FI
French
FR
Italian
IT
Dutch
NL
Portuguese
PT
Russian
RU
Swedish
SV
.
USER LOAD C TIME
USER LOAD C TIME
Code: 3AFE68802547 Rev A
Valid: from 01.11.2006 until the release of Rev D of the
manual
Contents: the main new features and changes which are not
yet updated to the manual. (Some features are already
included in Rev C, which is available in English only.) The
sections have a label NEW (= new feature), or CHANGE (=
changed feature), or DELETED (= deleted feature).
A summary of the updates is given below.
NEW:
Parameters and parameter values
380...480 V types
DELETED: Underload parameters
Motor torque (%)
P3706
P3709
Allowed operating area
P3705
P3708
P3704
P3707
USER LOAD C MODE
USER LOAD C MODE
.
Overload area
P3712
P3715
P3718
P3714
P3717
P3711
Underload area
P3710
P3713
P3716
Output frequency (Hz)
has been valid longer than
has been valid longer than
Update Notice
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-uh

Table of Contents