ABB ACH550-01 User Manual page 404

0.75...110 kw/1...150 hp
Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Air flow, 380...480 volt drives
The following table lists heat loss and air flow data for 380...480
volt drives at full load.
ACH550-01/UH-
02A4-4
03A3-4
04A1-4
05A4-4
06A9-4
08A8-4
012A-4
015A-4
023A-4
031A-4
038A-4
044A-4
059A-4
072A-4
077A-4
096A-4
124A-4
157A-4
180A-4
195A-4
392
Drive
Frame size
R1
R1
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R4
R4
R5
R5
R6
R6
R6
R6
ACH550 User's Manual
Heat loss
W
BTU/Hr
30
101
40
137
52
178
73
249
97
331
127
434
172
587
232
792
337
1151
457
1561
562
1919
667
2278
907
3096
1120
3825
1295
4423
1440
4918
1940
6625
2310
7889
2810
9597
3050
10416
Air flow
3
3
m
/h
ft
/min
44
26
44
26
44
26
44
26
44
26
44
26
44
26
88
52
88
52
134
79
134
79
280
165
280
165
280
165
250
147
250
147
405
238
405
238
405
238
405
238
00467918.xls A.7
Technical data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: