1004 JOGGING SEL
Defines the signal that activates the jogging function. Jogging uses Constant Speed 7 for speed reference and ramp
pair 2 for accelerating and decelerating. When the jogging activation signal is lost, the drive uses ramp stop to
decelerate to zero speed, even if coast stop is used in normal operation (parameter 2102). The jogging status can be
parameterized to relay outputs (parameter 1401). The jogging status is also seen in DCU Profile status bit 21.
0 =
– Disables the jogging function.
NOT SEL
1 =
1 – Activates/de-activates jogging based on the state of
DI
jogging inactive).
2...6 =
2...
6 – Activates jogging based on the state of the selected digital input. See
DI
DI
-1 =
1(
) – Activates jogging based on the state of
DI
INV
active).
-2...-6 =
2(
)...
DI
INV
DI
1103 REF1 SELECT
20 =
(
) – Defines the control panel as the reference source. A Stop command resets the reference to zero
KEYPAD
RNC
(R stands for reset.). Changing the control source (
21 =
(
) – Defines the control panel as the reference source. A Stop command does not reset the reference
KEYPAD
NC
to zero. The reference is stored. Changing the control source (
reference.
1401 RELAY OUTPUT 1
46 =
– Energize relay when a start delay is active.
START DELAY
52 =
– Energize relay when the jogging function is active.
JOG ACTIVE
1610 DISPLAY ALARMS
Controls the visibility of the following alarms:
• 2001, Overcurrent alarm
• 2002, Overvoltage alarm
• 2003, Undervoltage alarm
• 2009, Device overtemperature alarm.
For more information, see section Alarm listing.
0 =
– The above alarms are suppressed.
NO
1 =
– All of the above alarms are enabled.
YES
2101 START FUNCTION
8 =
– Immediate start from zero frequency.
RAMP
3023 WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running, it monitors for:
• Improper connections of input power to the drive output (the drive can display fault 35,
connections are detected).
• Ground faults (the drive can display fault 16, earth fault if a ground fault is detected). Also, see parameter 3017
.
EARTH FAULT
0 =
– No response to either of the above monitoring results.
DISABLE
1 =
– Displays a fault when this monitoring detects problems.
ENABLE
4010 SET POINT SEL
20 =
2
– Defines PID controller 2 output (parameter 0127
PID
OUT
6(
) – Activates jogging based on the state of the selected digital input. See
INV
1 (
1 activated = jogging active;
DI
DI
1 (
1 activated = jogging inactive;
DI
DI
1 to
2,
2 to
1) does not copy the reference.
EXT
EXT
EXT
EXT
1 to
2,
EXT
EXT
EXT
2
) as the reference source.
PID
OUTPUT
1 de-activated =
DI
1 above.
DI
1 de-activated = jogging
DI
1(
) above.
DI
INV
2 to
1) does not copy the
EXT
if improper
OUTPUT WIRING