ACH550 User's Manual
Alarm
Display
code
2008
PANEL LOSS
2009
DEVICE
OVERTEMP
2010
MOTOR TEMP
2011
UNDERLOAD
2012
MOTOR STALL
Diagnostics and maintenance
Description
Panel communication is lost and either:
• the drive is in local control mode (the control
panel displays HAND), or
• the drive is in remote control mode (AUTO) and
parameterized to accept start/stop, direction or
reference from the control panel.
To correct check:
• communication lines and connections
• parameter 3002
PANEL COMM ERR
• parameters in
Group 10: START/STOP/DIR
Group 11: REFERENCE SELECT
operation is AUTO).
Drive heatsink is hot. This alarm warns that a
fault may be near.
DEVICE OVERTEMP
R1...R4: 100°C (212°F)
R5/R6: 110°C (230°F)
Check for and correct:
• fan failure
• obstructions in the air flow
• dirt or dust coating on the heat sink
• excessive ambient temperature
• excessive motor load.
Motor is hot, based on either the drive's estimate or
on temperature feedback. This alarm warns that a
Motor Overload fault trip may be near.
• Check for overloaded motor.
• Adjust the parameters used for the estimate
(3005...3009).
• Check the temperature sensors and
MOTOR TEMP MEAS
Motor load is lower than expected. This alarm
warns that a Motor Underload fault trip may be
near. Check:
• motor and drive ratings match (motor is NOT
undersized for the drive)
• settings on parameters 3013 to 3015.
Motor is operating in the stall region. This alarm
warns that a Motor Stall fault trip may be near.
(if drive
Group 35:
parameters.
and