System Specifications
Power Enclosure Components
Input current
AC Input
Nominal input voltage
Nominal line frequency
Recommended AC service
AC Power Cord Length

Environmental Specifications

Table 15: Cisco NCS 6000 FCC Environmental Specifications
Temperature
Humidity
Altitude
FCC airflow
Power system airflow
Air exhaust temperature
50 A max at –48 VDC
40 A max at –60 VDC
60 A at –40 VDC (maximum)
Single-phase
200 to 240 VAC (range 180 to 264 VAC)
50/60 Hz (range 47 to 63 Hz)
20-A (North America) dedicated branch circuit
16-A (International) dedicated branch circuit
167 in. (4.25 m)
Operating, nominal: 41 to 104°F (5° to 40°C)
Operating, short-term: 23 to 122°F (–5° to 50°C)
Nonoperating: –40 to 158°F (–40° to 70°C)
Operating, nominal: 5 to 85%, noncondensing
Operating, short-term: 5 to 90%, noncondensing
Nonoperating: 5 to 93%, noncondensing
Operating: –200 to 13,800 ft (–61 to 4206 m) at 104°F (40°C)
Nonoperating: Up to 16,000 ft (4877 m) at –13°F (–25°C), short-term
2000 CFM (Cubic Feet per Minute)
Up to 56,600 liters per minute
Up to 3400 liters per minute
122°F (50°C)—at room temperatures of 95 to 102°F (35 to 39°C)
140°F (60°C)—maximum exhaust temperature on a fully loaded system during worst-case operating
conditions (50°C and 6000 ft altitude)