Power Specifications - Cisco Network Convergence System 6000 Fabric Card Chassis Hardware Installation Manual

Table of Contents

Advertisement

Power Specifications

Weights
FCC as shipped
FCC in shipping crate with pallet
FCC, fully loaded with power enclosure,
cards, and cosmetics
Floor Loading
FCC in rack footprint(floor contact area)
Maximum floor loading
Fabric Chassis Cooling
FCC airflow
DC power system airflow
AC power system airflow
Power Specifications
Table 14: Cisco NCS 6000 FCC Power Specifications
Power Enclosure Components
Power Trays
Power modules (PMs)
Power control modules (PCMs)
Power Redundancy (N+N)
DC Input
Nominal input voltage
Cisco Network Convergence System 6000 Fabric Card Chassis Hardware Installation Guide
128
708 lb (321 kg)
925 lb (420 kg)
1130 lb (513 kg)
FCC: 6.9 sq ft (0.64 sq m)
164 lb/sq ft
Two fan trays
Up to 1980 cubic feet (56,6000 liters) per minute
Up to 120 cubic feet (3400 liters) per minute
Up to 88 cubic feet (2500 liters) per minute
Either four AC or four DC power trays. AC and DC power trays cannot be mixed.
The AC power tray has three slots for AC PMs. The DC power tray has four slots for
DC PMs.
Two PCMs are preinstalled in the power enclosure (one per each set of power trays).
AC: Up to 12 power modules can be installed, and only 6 are needed to be active at
any time. This allows support for 6+6 power redundancy by using two independent AC
power sources (6 feeds each).
DC: Up to16 power modules can be installed, and only 8 are needed to be active at any
time. This allows support for 8+8 power redundancy through "A" and "B" battery plant
feeds.
–48 VDC or –60 VDC (tolerance range: –40 to –72 VDC)