Dc Power System - Cisco Network Convergence System 6000 Fabric Card Chassis Hardware Installation Manual

Table of Contents

Advertisement

Installing the Power Components
The 19-inch tie-down bar and screws are not supplied by Cisco. You can order these parts from a
Note
commercial vendor such as Panduit.
Figure 27: 19-Inch Tie-Down Bar
1

DC Power System

A DC-powered Cisco NCS 6000 FCC contains four DC power trays that are part of the FCC power enclosure
(Figure 5: FCC Power Enclosure—Front and Rear
referred to as power shelf 0 (PS0), and the lower two power trays (PT2 and PT3) are referred to as power
shelf 1 (PS1).
module (PCM) with its own I/O power switch.
The DC power tray has four slots for PMs. The DC power trays are field-replaceable (after power down),
however the PMs are hot-swappable.
For N+N redundancy, "A" power feeds must power the upper two DC power trays and "B" power feeds must
power the lower two DC power trays (not all of the PM bays need to be filled). This allows the system to
balance its load across the two set of power trays and across the power modules within each tray.
The following table lists the DC input current and voltage specifications.
Tie-down bar
Figure 3: Cisco NCS 6000 FCC Slot
Cisco Network Convergence System 6000 Fabric Card Chassis Hardware Installation Guide
Views). The upper two power trays (PT0 and PT1) are
Numbers. Each set of power trays has a power control
DC Power System
43

Advertisement

Table of Contents
loading

Table of Contents