Power Specifications - Cisco NCS 4000 Series Hardware Installation

Hide thumbs Also See for NCS 4000 Series:
Table of Contents

Advertisement

Power Specifications

Aisle spacing
Weights
Chassis as shipped
Chassis in shipping crate with pallet
Chassis, fully loaded with power, fan trays, cards,
and cosmetics
Floor Loading
Chassis in rack footprint(floor contact area)
Maximum floor loading
Chassis Cooling
Chassis airflow
DC power system airflow
AC power system airflow
Power Specifications
Table 21: Cisco NCS 4016 Chassis Power Specifications
Power Specifications
Power Trays
DC power tray
AC power tray
Power Redundancy
DC
Hardware Installation Guide for Cisco NCS 4000 Series
144
To install chassis (front): 48 in. (122 cm)
To service FRUs (front): 31.7 in. (80.5 cm)
To service FRUs (rear): 14.0 in. (35.6 cm)
250 lb (113.5 kg)
319 lb (145 kg)
412 lb (187 kg)
Chassis: 2.5 sq ft (0.23 sq m)
263 lb/sq ft
Two fan trays
45,300 liters per minute
6796 liters per minute
5097 liters per minute
Either two AC or two DC power trays (cannot mix
AC and DC power trays)
Up to four DC PMs per tray
Up to four AC PMs per tray
Up to 8 power modules can be installed, and only
7are needed to be active at any time. This allows
support for 7+1 power redundancy and A and B
battery plant dual feeds redundancy.