2.6

Cooling-water data

Description
Maximum supply pressure
Maximum allowable system differential pressure
Minimum required pressure differential across supply and return
Supply temperature range
Water type
Maximum particle size
Acidity
Hardness
Resistivity
Materials in contact with
cooling water
Water inlet connection
Water outlet connection
Table 11 - Water cooling system data
Rating
6.9
100
5.5
Refer to
Table 13
Refer to
Table 12
Treated or non-corrosive industrial
0.03
6.5 to 8.0
<100
1k ≤ ρ ≤ 1000k
Stainless steel, Nitrile, PTFE, brass and
fluoroelastomer
3/8 inch BSP male quick connector
3/8 inch BSP female quick connector
Units
barg
psig
bar
2
mm
pH
ppm of CaCO
(<100 mg of CaCO
per litre)
3
3
ohm-cm