SMA Solar Technology AG
7.5.2

Explanation of the Error Tables

You will find the following information in the error tables in the following sections:
Error no.
Explanation
1301
Left-hand rotating magnetic field
is connected.
3803
DC current of PV array is too high.
0104
Grid voltage is too high.
Position
A
B
7.5.3

Error Numbers 01xx to 13xx - Disturbance on the Utility Grid

After a grid failure, the inverter monitors the utility grid for a specific period before reconnecting. When the inverter
monitors the utility grid after a grid error, the grid monitoring time is complied with. Certain errors, such as grid errors,
cause the inverter to shut down. In this case, the instantaneous value TmsRmg indicates the time for which the inverter
monitors the utility grid before reconnecting. This grid monitoring time can be defined in parameter GdErrTm.
Error no. Explanation
0103*
Grid voltage is too high. Overvolt-
age detected by redundant moni-
toring.
0104*
Grid voltage is too high. Overvolt-
age detected by standard monitor-
ing.
0203*
Grid voltage is too low. Undervolt-
age detected by redundant moni-
toring.
0204*
Grid voltage is too low. Undervolt-
age detected by standard monitor-
ing.
0205*
Not permitted grid frequency
change or grid synchronization
not possible
User Manual
Explanation
Behavior of the inverter: disturbance level S1, disturbance level S2
• s / min: waiting time
• C: system-specific
• D: day change
• Q: waiting for acknowledgement
• W: warning
Reset
A
S1
S2
R
30 s
Q
1 min
D
W
C
Inverter behavior
Corrective measures
S1
S2
R
30 s
30 s
• Check the grid voltage.
• Check grid connections.
• Check stability of the utility grid.
C
C
• Make sure the external fuses work
• Make sure the AC cable connections
30 s
30 s
30 s
30 s
30 s
30 s
B
Corrective measures
• Check phase position.
x
• Check DC input current.
• Check grid voltage.
properly.
are tight.
SCCPXT-E7-BA-en-58
7 Troubleshooting
67