11 Operating Data and Parameters
Name
Description
P-WSubValRun
Substitute value for ac-
tive power limitation in
normal feed-in operation
during communication
disturbance
Q-VArSubVal
Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance
PF-PFSubVal
Substitute value for cos φ
outside of normal feed-in
operation during commu-
nication disturbance
The lower limit is defined
by the parameter PFAb-
sMin.
PF-PFExtSubVal Substitute value for exci-
tation type during com-
munication disturbance
130
SCCPXT-E7-BA-en-58
Value/range
Explanation
0 kW to 550 kW
Sunny Central 500CP XT
0 kW to 700 kW
Sunny Central 630CP XT
0 kW to 792 kW
Sunny Central 720CP XT
0 kW to 836 kW
Sunny Central 760CP XT
0 kW to 880 kW
Sunny Central 800CP XT
0 kW to 935 kW
Sunny Central 850CP XT
0 kW to 990 kW
Sunny Central 900CP XT
0 kW to 1100 kW
Sunny Central 1000CP XT
−245 kVAr to
Sunny Central 500CP XT
+245 kVAr
−310 kVAr to
Sunny Central 630CP XT
+310 kVAr
−346 kVAr to
Sunny Central 720CP XT
+346 kVAr
−365 kVAr to
Sunny Central 760CP XT
+365 kVAr
−385 kVAr to
Sunny Central 800CP XT
+385 kVAr
−409 kVAr to
Sunny Central 850CP XT
+409 kVAr
−433 kVAr to
Sunny Central 900CP XT
+433 kVAr
−485 kVAr to
Sunny Central 1000CP XT
+485 kVAr
0.5 ... 1
OvExt
Overexcited
UnExt
Underexcited
SMA Solar Technology AG
Default
value
550 kW
700 kW
792 kW
836 kW
880 kW
935 kW
990 kW
1,100 kW
0 kVAr
1
OvExt
User Manual