SMA SUNNY CENTRAL 500CP XT User Manual page 116

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

11 Operating Data and Parameters
Errors and warnings relating to the reactive power setpoint
Name
Q-VArModFailStt
Status messages of the reactive power setpoint
Name
Q-VArModStt
Displacement power factor and power setpoint
Name
PF
PFExt
P-WSpt
116
SCCPXT-E7-BA-en-58
Display
Description
Off
No mode for specifying the reactive power setpoint has been se-
lected.
Ok
A mode for specifying the reactive power setpoint has been selected
and no error is present.
ComFail
The mode VArCtlCom or PFCtlCom has been selected and the ex-
pected signal with a valid reactive power setpoint has been absent
for at least five minutes.
AnInFail
The mode VArCnstNomAnIn or PFCnstAnIn has been selected
and the value measured at the analog input is less than 2 mA.
ComInvalid
The mode VArCtlCom or PFCtlCom has been selected and there is
invalid content in the power setpoint information.
Display
Description
Off
No mode for specifying the reactive power setpoint has been se-
lected.
VdcMax
The reactive power is limited due to DC voltage being too high.
VacLimMax
The reactive power is limited due to AC voltage being too high.
VacLimMin
The reactive power is limited due to the AC voltage being too low.
SMaxVdcHigh
The maximum apparent power value is reduced. If the maximum DC
voltage increases, the reactive power is reduced.
SMax
The reactive power is limited by the maximum apparent power.
Tmp
The reactive power is limited by temperature derating.
AmpAC
The reactive power is limited via an AC current limitation.
P
The reactive power is limited due to the priority of the active power
setpoint.
FrtLim
The reactive power is limited due to the FRT voltage limit.
Display
Description
Current displacement power factor cos φ
OvExt
Overexcited
UnExt
Underexcited
Current power specification