11 Operating Data and Parameters
Name
Description
DevFunc*
Manages the Sunny String-Moni-
tors
* To change these parameters, you must enter the installer password.

11.2.3 Sunny String-Monitor

Name
Description
TMittelung*
Duration of averaging of current
measurements
String Anzahl*
Number of detected strings
SW Version
Current firmware version
SSM Identifier* Identification number of Sunny
String-Monitor
Group String
Assigns strings to their respective
1*
group
Group String*
All groups
No.of String 1* Number of connected strings in
the respective group
No.of Strings*
All groups
Monitoring1
Start of monitoring of strings in
On*
group 1
Monitoring1
End of monitoring of strings in
Off*
group 1
142
SCCPXT-E7-BA-en-58
Value/range
Explanation
AutoDetect_
Searches for all Sunny String-
SSMU
Monitors and deletes previ-
ously detected Sunny String-
Monitors
DetectSSMU
Searches for undetected
Retry
Sunny String-Monitors only
DelAll_SSMU
Deletes all detected
Sunny String-Monitors
Factory
Resets all parameters to default
settings.
Value/range
Explanation
0 s to 6,000 s
0 to 8
1 to 40
Value cannot be changed
1 to 99
0 to 3
Parameter exists for all eight
groups
0 to 3
1 to 4
Parameter exists for all eight
groups
If you wish to use this function,
contact us (see Section 13,
page 153).
1 to 4
0:00 a.m. to
Parameter exists for all eight
11:59 p.m.
groups
Configure the string settings
preferably via the Sunny Cen-
tral String-Monitor Controller.
0:00 a.m. to
Parameter exists for all eight
11:59 p.m.
groups
Configure the string settings
preferably via the Sunny Cen-
tral String-Monitor Controller.
SMA Solar Technology AG
Default
value
0
Default
value
30 s
0
0
0
0
0
0
User Manual