SMA SUNNY CENTRAL 500CP XT User Manual page 122

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

11 Operating Data and Parameters
Name
Description
P-W
Active power limit in kW
The active power cannot
exceed Pmax.
P-WNom
Limitation of active
power in %
WCtlHz-
Activation of frequency-
Mod**
dependent active power
limitation
P-HzStr**
Starting point of fre-
quency control
P-HzStop**
End point of frequency
control
P-HzStop-
Minimum frequency at
Min**
end point of frequency
control
P-WGra**
Gradient of active power
limitation in case of ac-
tive power limitation de-
pendent on the fre-
quency
Qlimit*
Reactive power of device 0 kVAr to 245 kVAr
122
SCCPXT-E7-BA-en-58
Value/range
Explanation
0 kW to 1000 kW
Sunny Central 500CP XT
0 kW to 1000 kW
Sunny Central 630CP XT
0 kW to 1000 kW
Sunny Central 720CP XT
0 kW to 1000 kW
Sunny Central 760CP XT
0 kW to 1000 kW
Sunny Central 800CP XT
0 kW to 1000 kW
Sunny Central 850CP XT
0 kW to 1000 kW
Sunny Central 900CP XT
0 kW to 1100 kW
Sunny Central 1000CP XT
0 % ... 100 %
Off
Deactivated
CurveHys
Procedure with hysteresis
Curve
Procedure without hysteresis
Country-specific
Country-specific
Country-specific
1%/Hz to 100%/Hz ‒
Sunny Central 500CP XT
0 kVAr to 310 kVAr
Sunny Central 630CP XT
0 kVAr to 346 kVAr
Sunny Central 720CP XT
0 kVAr to 365 kVAr
Sunny Central 760CP XT
0 kVAr to 385 kVAr
Sunny Central 800CP XT
0 kVAr to 409 kVAr
Sunny Central 850CP XT
0 kVAr to 433 kVAr
Sunny Central 900CP XT
0 kVAr to 485 kVAr
Sunny Central 1000CP XT
SMA Solar Technology AG
Default
value
550 kW
700 kW
792 kW
836 kW
880 kW
935 kW
990 kW
1,100 kW
100 %
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
245 kVAr
310 kVAr
346 kVAr
365 kVAr
385 kVAr
409 kVAr
433 kVAr
485 kVAr
User Manual