Grid Monitoring And Grid Limits - SMA SUNNY CENTRAL 500CP XT User Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
QoDDccOffDe-
Delay time until the DC
lay*
switchgear opens in the
operating state
"Q at Night"
* You can only view this parameter.
** To change this parameter, you must enter the installer password.
*** To view or change this parameter, you must enter the installer password.

11.2.1.2 Grid Monitoring and Grid Limits

To change these parameters, you must enter the installer password.
Name
Description
VRtg
Nominal line-to-line volt-
age of the utility grid
VCtlMax
Threshold for overvolt-
age release level 3
VCtlMaxTm
Delay time for overvolt-
age level 3
VCtlhhLim
Threshold for overvolt-
age release level 2
VCtlhhLimTm
Delay time for overvolt-
age level 2
VCtlhLim
Threshold for overvolt-
age release level 1
VCtlhLimTm
Delay time for overvolt-
age level 1
VCtllLim
Threshold for undervolt-
age release level 1
VCtllLimTm
Delay time for undervolt-
age level 1
VCtlllLim
Threshold for undervolt-
age release level 2
VCtlllLimTm
Delay time for undervolt-
age level 2
VCtlMin
Threshold for undervolt-
age release level 3
VCtlMinTm
Delay time for undervolt-
age level 3
User Manual
Value/range
Explanation
0 s ... 86,400 s
Range
Explanation
1 V to 70,000 V
100% ... 150%
0 ms ...
1,000,000 ms
100% ... 150%
0 ms ...
1,000,000 ms
100% ... 150%
0 ms ...
1,000,000 ms
0% ... 100%
0 ms ...
1,000,000 ms
0% ... 100%
0 ms ...
1,000,000 ms
0% ... 100%
0 ms ...
1,000,000 ms
11 Operating Data and Parameters
Default
value
3,600 s
Default
value
20,000 V
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
Country-
specific
SCCPXT-E7-BA-en-58
133