4 Commissioning
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• After switching off the product, wait until any hot components have cooled down sufficiently.
• Wear suitable personal protective equipment for all work on the product.
Procedure:
1. Switch the inverter to Stop (see Section 5.2.1, page 50).
2. Connect the supply voltage (see Section 5.3.1, page 52).
3. Set the hygrostat to the minimum value. To do this, pull the selector switch out slightly.
Tip: the hygrostat is adjusted correctly if the relay of the hygrostat emits an audible click.
4. Check whether the heating elements are radiating heat after a delay time of five minutes.
If the heating elements are not radiating heat, contact us (see Section 13 "Contact", page 153).
5. Reset the hygrostat to the initial value. To do this, press the selector switch back towards the hygrostat. The initial
value of the hygrostat is indicated on the hygrostat.
4.6

Configuration

4.6.1

Configuring the Network Settings on the Computer

Before your computer can communicate with the inverter, you must set the computer to the network settings of the
inverter. The network settings include the IP address, subnet mask, gateway and DNS server address.
The communication interface of the inverter has three LAN interfaces to the connected nodes. The IP address to be
configured in your computer depends on whether the computer is connected to the service interface of the inverter, the
control network or the monitoring network.
Network
LAN1: Service interface of the inverter
LAN2: Control network
LAN3: Monitoring network
* This IP address cannot be changed.
Administrator rights in the operating system
To commission the communication unit, you need to have the appropriate administrator rights to change the
network settings of the computer.
• Contact your network administrator if you are uncertain about administrator rights.
Procedure:
1. Note down the IP address of the computer.
2. Adapt the IP address of the computer to the address range of the communication unit.
34
SCCPXT-E7-BA-en-58
CAUTION
Default IP address
192.168.100.2*
172.24.1.51