SMA SUNNY CENTRAL 500CP XT User Manual page 123

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
Qmax**
Limitation of reactive
power
QoDQmax*
Limitation of reactive
power in the operating
state "Q at Night".
The reactive power can-
not exceed Qlimit.
QEnsure*
Guaranteed reactive
power
PFAbsMin*
Limitation of the displace-
ment power factor cos φ
User Manual
Value/range
Explanation
0 kVAr to 245 kVAr
Sunny Central 500CP XT
0 kVAr to 310 kVAr
Sunny Central 630CP XT
0 kVAr to 346 kVAr
Sunny Central 720CP XT
0 kVAr to 365 kVAr
Sunny Central 760CP XT
0 kVAr to 385 kVAr
Sunny Central 800CP XT
0 kVAr to 409 kVAr
Sunny Central 850CP XT
0 kVAr to 433 kVAr
Sunny Central 900CP XT
0 kVAr to 485 kVAr
Sunny Central 1000CP XT
0 kVAr to 165 kVAr
Sunny Central 500CP XT
0 kVAr to 210 kVAr
Sunny Central 630CP XT
0 kVAr to 238 kVAr
Sunny Central 720CP XT
0 kVAr to 251 kVAr
Sunny Central 760CP XT
0 kVAr to 264 kVAr
Sunny Central 800CP XT
0 kVAr to 281 kVAr
Sunny Central 850CP XT
0 kVAr to 297 kVAr
Sunny Central 900CP XT
0 kVAr to 330 kVAr
Sunny Central 1000CP XT
0 kVAr to 245 kVAr
Sunny Central 500CP XT
0 kVAr to 310 kVAr
Sunny Central 630CP XT
0 kVAr to 346 kVAr
Sunny Central 720CP XT
0 kVAr to 365 kVAr
Sunny Central 760CP XT
0 kVAr to 385 kVAr
Sunny Central 800CP XT
0 kVAr to 409 kVAr
Sunny Central 850CP XT
0 kVAr to 433 kVAr
Sunny Central 900CP XT
0 kVAr to 485 kVAr
Sunny Central 1000CP XT
0.5 ... 1
11 Operating Data and Parameters
Default
value
245 kVAr
310 kVAr
346 kVAr
365 kVAr
385 kVAr
409 kVAr
433 kVAr
485 kVAr
165 kVAr
210 kVAr
238 kVAr
251 kVAr
264 kVAr
281 kVAr
297 kVAr
330 kVAr
0 kVAr
0.9
SCCPXT-E7-BA-en-58