SMA Solar Technology AG
Figure 19: GFDI
Position
Designation
A
GFDI

10.2.3.3 Remote GFDI

Depending on the order option, ground fault monitoring in the inverter may be carried out via ground fault detection
and interruption with motor drive, in short "Remote GFDI". This grounds one terminal of the PV array. Remote GFDI also
enables automatic error processing. This reduces downtimes and avoids service calls due to temporary insulation
errors such as when condensation occurs on the PV modules. Remote GFDI is performed via a high-performance K-type
circuit breaker with adjustable operating current. The remote GFDI is integrated in the inverter and connected between
an input busbar and the grounding busbar.
Figure 20: Remote GFDI
Position
A
If the Remote GFDI trips, initially a temporary error will be assumed and a motor drive will close the Remote GFDI after
a defined waiting time. No external switch command is required to close the tripped Remote GFDI. The inverter can
switch back to feed-in operation after a waiting time. In the default setting of the inverter, the software will attempt to
start the Remote GFDI up to three times per day. If the Remote GFDI is tripped on several consecutive days, the
software assumes a permanent insulation error and the inverter will no longer switch back on. In this case, a qualified
person will need to check and, if necessary, repair the insulation and then acknowledge the error.
User Manual
Designation
Remote GFDI
10 Function Description
SCCPXT-E7-BA-en-58
89