11 Operating Data and Parameters
Name
Description
QoDQ-Var**
Limitation of the external
reactive power setpoint
in the operating state
"Q at Night"
Q-VArNom
Reactive power in %
QoDQ-
Reactive power in% in
VArNom
the operating state
"Q at Night"
PF-PF
Displacement power fac-
tor cos φ
The lower limit is defined
by the parameter PFAb-
sMin.
PF-PFExt
Excitation of the dis-
placement power factor
cos φ
PF-PFStr**
Displacement power fac-
tor cos φ at characteristic
curve point 1
The lower limit is defined
by the parameter PFAb-
sMin.
PF-PFExtStr**
Excitation of the dis-
placement power factor
cos φ at characteristic
curve point 1
126
SCCPXT-E7-BA-en-58
Value/range
Explanation
−165 kVAr to
Sunny Central 500CP XT
+165 kVAr
−210 kVAr to
Sunny Central 630CP XT
+210 kVAr
−248 kVAr to
Sunny Central 720CP XT
+248 kVAr
−251 kVAr to
Sunny Central 760CP XT
+251 kVAr
−264 kVAr to
Sunny Central 800CP XT
+264 kVAr
−281 kVAr to
Sunny Central 850CP XT
+281 kVAr
−297 kVAr to
Sunny Central 900CP XT
+297 kVAr
−330 kVAr to
Sunny Central 1000CP XT
+330 kVAr
−100 % ... +100 %
−100 % ... +100 %
0.5 ... 1
OvExt
Overexcited
UnExt
Underexcited
0.5 ... 1
OvExt
Overexcited
UnExt
Underexcited
SMA Solar Technology AG
Default
value
0 kVAr
0 %
0 %
1
OvExt
0.9
OvExt
User Manual