11 Operating Data and Parameters
Name
DcCfg.AmpMax[4]
DcCfg.AmpMax[5]
DcCfg.AmpMax[6]
DcCfg.AmpMax[7]
DcCfg.AmpMax[8]
MaxTol
DevFunc
Ackn
AlarmEna
144
SCCPXT-E7-BA-en-58
Description
Value/range
Maximum current of
0 A to 500 A
input 4
Maximum current of
0 A to 500 A
input 5
Maximum current of
0 A to 500 A
input 6
Maximum current of
0 A to 500 A
input 7
Maximum current of
0 A to 500 A
input 8
Tolerance in percent
0.1 % ... 100  %
by which the input
current may deviate
from the mean value
Device function
---
ResetMeasuring
Factory
Acknowledge errors
---
Quit
Activation of the error
---
analysis
Off
On
SMA Solar Technology AG
Explanation
Default, no action
Restarts the algorithm. All measured
value are deleted.
Resets all parameters to default set-
tings
Default, no action
Acknowledgment of the present er-
ror
Default, no action
No error analysis. Only measured
value are sent.
Error analysis activated. Error mes-
sages are generated, if deviations
occur (see Section 11.1.4.2,
page 120).
Default
value
0 A
0 A
0 A
0 A
0 A
4.0 %
---
---
---
User Manual