7 Troubleshooting
Error no. Explanation
0404*
Frequency change per second too
high for grid operation
0502*
Power frequency is too low. Power
frequency disturbance detected by
standard monitoring.
0503*
Power frequency is too high.
Power frequency disturbance de-
tected by standard monitoring.
0504*
Power frequency is too low. Power
frequency disturbance detected by
redundant monitoring.
0505*
Power frequency is too high.
Power frequency disturbance de-
tected by redundant monitoring.
0506*
The inverter has detected a stand-
alone grid and has disconnected
from the utility grid.
0801*
One line conductor of the utility
grid has failed.
0802*
1301
Left-hand rotating magnetic field is
connected.
1500
The conditions for grid reconnec-
tion have not yet been reached af-
ter a grid error.
* Depending on the parameterization, the disturbance message may have to be acknowledged manually.
7.5.4
Error Numbers 34xx to 40xx - Disturbance on the PV Array
Error no. Explanation
3403
PV array voltage is too high.
3404
Open-circuit voltage is too high.
Disturbance detected by standard
monitoring.
3406
The DC voltage is too high.
68
SCCPXT-E7-BA-en-58
Inverter behavior
Corrective measures
S1
S2
R
30 s
30 s
‒
‒
30 s
30 s
‒
• Check power frequency.
• Check the display of the grid monitoring
• Make sure the fuses in the load circuit
30 s
30 s
‒
30 s
30 s
‒
30 s
30 s
‒
W
W
‒
• Check power frequency.
30 s
30 s
‒
• Check the grid voltage.
• Make sure the external fuses work
• Make sure the AC cable connections
30 s
Q
‒
• Check the phase position.
• Make sure all fuses are switched on.
W
W
‒
• Check the power frequency and grid
Inverter behavior
Corrective measures
S1
S2
R
15
30
‒
• Check the DC voltage.
min
min
• Check the module wiring and system
15
30
‒
min
min
15
30
‒
min
min
SMA Solar Technology AG
relay.
function properly.
properly.
are tight.
voltage.
design.
User Manual