11.2.1.4 Insulation monitoring

Name
Description
IsoMod
Hardware selection for
insulation monitoring and
ground-fault monitoring
IsoErrIgn*
Ignore insulation error
RemMntSvc
PV array grounding is
deactivated.
RisoCtlWarn
Warning threshold for
the insulation monitoring
device iso-PV1685
PvVtgRisoStart
Start voltage of insulation
measurement
User Manual
Value/range
Explanation
---
No insulation monitoring and
ground-fault monitoring
Gfdi
GFDI
RemGdfi
Remote GFDI
IsoMeas
Insulation monitoring
IsoMeasGfdi
Insulation monitoring with GFDI
IsoMeasRemGfdi
Insulation monitoring with Re-
mote GFDI
SoftGndDold
Soft Grounding
IsoMeasSoftGndD
Insulation monitoring with
Soft Grounding
USRemGFDI
Remote GFDI for the U.S.
AutoUSRemGFDI
Automatic Remote GFDI for the
U.S.
Off
Deactivated
On
Activated
Run
Error is only ignored when the in-
verter is in feed-in operation.
Off
Deactivated
On
Activated
0 kΩ to 500 kΩ
0 V to 1,200 V
Sunny Central 500CP XT
Sunny Central 630CP XT
Sunny Central 720CP XT
Sunny Central 760CP XT
Sunny Central 800CP XT
Sunny Central 850CP XT
Sunny Central 900CP XT
Sunny Central 1000CP XT
11 Operating Data and Parameters
Default
value
---
Off
Off
45 kΩ
250 V
SCCPXT-E7-BA-en-58