Function Test
4.5.1
Checking the Fans
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 5, page 50).
Procedure:
1. Switch the inverter to Stop.
2. Connect the supply voltage (see Section 5.3.1, page 52).
☑ The fans start to run for a few moments.
✖ The fans do not start up?
• Contact SMA Service Line.
4.5.2
Checking the Heating Elements and Hygrostat
Figure 11: Position of the heating element and the hygrostat
Position
A
B
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 5, page 50).
User Manual
Designation
Hygrostat
Heating element
DANGER
DANGER
4 Commissioning
SCCPXT-E7-BA-en-58