10 Function Description

10.5.2.3 Dynamic Undervoltage Detection

The dynamic undervoltage detection extends the grid support in the event of undervoltage and changes the switch-off
behavior. The grid limits, which are stepped by default, are replaced by a continuous grid-limit function.
V /V [%]
Grid
100
1
2
Figure 43: Maximum duration of a voltage dip that the inverter can work through without disconnecting from the utility grid
Position
Parameter
1
VCtllLim
2
VCtlllLim
3
A
VCtllCharTm
B
VCtllLimTm
The function of the dynamic undervoltage detection is activated via the parameter VCtllCharEna.
The function of the dynamic undervoltage detection is activated by default for Romania.
112
SCCPXT-E7-BA-en-58
A
Description
Grid voltage limit level 1
Grid voltage limit level 2
Time at which the inverter disconnects from the utility grid.
The delay time of the dynamic undervoltage detection defines the in-
tersection of the continuous grid-limit function with the time axis.
Delay time for grid limit level 1
Grid voltage
Dynamic grid support (FRT)
Grid disconnection
B
SMA Solar Technology AG
t
3
User Manual