11 Operating Data and Parameters
Name
Description
Q-VArGra-
Reactive power gradient
NomPos**
at a positive change of
nominal voltage
Q-VArGra-
Reactive power gradient
NomNeg**
at a negative change of
nominal voltage
PF-PFSubVal-
Substitute value cos φ in
Run
normal feed-in operation
during communication
disturbance
The lower limit is defined
by the parameter PFAb-
sMin.
PF-PFExtSub-
Substitute value of the ex-
ValR
citation type in normal
feed-in operation during
communication distur-
bance
PwrMon-
Mode used in the event
ErrMod
of communication distur-
bance
PwrMonErrTm
Communication down-
time until substitute val-
ues are used
QoDEna
Activates/deactivates the
function "Q at Night"
132
SCCPXT-E7-BA-en-58
Value/range
Explanation
0%/V to 40.06%/V
Sunny Central 500CP XT
0%/V to 31.47%/V
Sunny Central 630CP XT
0%/V to 27.82%/V
Sunny Central 720CP XT
0%/V to 26.35%/V
Sunny Central 760CP XT
0%/V to 25.04%/V
Sunny Central 800CP XT
0%/V to 23.56%/V
Sunny Central 850CP XT
0%/V to 22.25%/V
Sunny Central 900CP XT
0%/V to 22.25%/V
Sunny Central 1000CP XT
0%/V to 40.06%/V
Sunny Central 500CP XT
0%/V to 31.47%/V
Sunny Central 630CP XT
0%/V to 27.82%/V
Sunny Central 720CP XT
0%/V to 26.35%/V
Sunny Central 760CP XT
0%/V to 25.04%/V
Sunny Central 800CP XT
0%/V to 23.56%/V
Sunny Central 850CP XT
0%/V to 22.25%/V
Sunny Central 900CP XT
0%/V to 22.25%/V
Sunny Central 1000CP XT
0.5 ... 1
OvExt
Overexcited
UnExt
Underexcited
LastVal
Use of last default values re-
ceived
SubVal
Use of substitute values
1 s to 999 s
Off
"Q at Night" function disabled
On
"Q at Night" function enabled
SMA Solar Technology AG
Default
value
0%/V
0%/V
1
OvExt
LastVal
300 s
Off
User Manual