SMA SUNNY CENTRAL 500CP XT User Manual page 131

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
Q-VArSubVal-
Substitute value for reac-
Run
tive power setpoint in
normal feed-in operation
during communication
disturbance
Q-VLockInW** Voltage value from
which the Q(V) charac-
teristic curve is activated,
in % relative to the nomi-
nal voltage
Q-VLock-
Voltage value from
OutW**
which the Q(V) charac-
teristic curve is deacti-
vated, in% based on the
nominal voltage
Q-VLock-
Waiting time for activa-
InTm**
tion of the Q(V) charac-
teristic curve
Q-VLock-
Waiting time for deacti-
OutTm**
vation of the Q(V) char-
acteristic curve
User Manual
Value/range
Explanation
−245 kVAr to
Sunny Central 500CP XT
+245 kVAr
−310 kVAr to
Sunny Central 630CP XT
+310 kVAr
−346 kVAr to
Sunny Central 720CP XT
+346 kVAr
−365 kVAr to
Sunny Central 760CP XT
+365 kVAr
−385 kVAr to
Sunny Central 800CP XT
+385 kVAr
−409 kVAr to
Sunny Central 850CP XT
+409 kVAr
−433 kVAr to
Sunny Central 900CP XT
+433 kVAr
−485 kVAr to
Sunny Central 1000CP XT
+485 kVAr
0 % ... 100 %
0 % ... 100 %
0 s to 100 s
0 s to 100 s
11 Operating Data and Parameters
Default
value
0 kVAr
0 %
0 %
2 s
2 s
SCCPXT-E7-BA-en-58
131