Grid Support - SMA SUNNY CENTRAL 500CP XT User Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
NormVac*
Measuring range end
value of AC voltage
measurement
NormAac*
Measuring range end
value of AC current mea-
surement
ManResOvrVol Manual activation after
overvoltage
ManResUndr-
Manual activation after
Vol
undervoltage
ManResOvrFrq Manual activation after
overfrequency
ManResUndr-
Manual activation after
Frq
underfrequency
ManResPID
Manual activation after
interruption by passive is-
landing detection
ManResPLD
Manual activation after
interruption due to distur-
bance in a line conduc-
tor
* You can only view this parameter.

11.2.1.3 Grid Support

Name
Description
FRTMod*
Dynamic grid support op-
erating modes
FRTSwOffTm*
Deactivation delay of the
LVRT
FRTArGra-
Scaling of the K factor
Nom**
for LVRT
User Manual
Range
Explanation
1 V ... 1,000 V
1 A ... 3,000 A
Sunny Central 500CP XT ...
Sunny Central 900CP XT
1 A ... 3,500 A
Sunny Central 1000CP XT
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
Value/range
Explanation
FRT_BDEW
Complete dynamic grid support
FRT_Partial
Limited dynamic grid support
FRT_SDLWindV
Complete dynamic grid support
with FRT characteristic curve
FRT_Off
Deactivation of dynamic grid sup-
port
0 ms to 10,000 ms
0 ... 10
Values up to max. 2 are recom-
mended. Values larger than 2
can lead to unstable plant behav-
ior.
11 Operating Data and Parameters
Default
value
862 V
2,219 A
2,958 A
Off
Off
Off
Off
Off
Off
Default
value
Country-
specific
Country-
specific
Country-
specific
SCCPXT-E7-BA-en-58
135