Name
Description
WGraReco-
Activation of the decou-
nEna**
pling protection ramp for
reconnection
P-VtgGra-
Active power gradient
Nom**
for voltage-dependent
active power limitation
P-VtgEna
Activation of voltage-de-
pendent active power
limitation
P-VtgNomP1
Voltage at point 1
P-VtgNomP2
Voltage at point 2
P-VtgAtMin
Minimum active power
with voltage-dependent
active power limitation
PwrApLimit-
Prioritization of reactive
Prio***
power or active power
SDLimCom-
Selection of the SDLimit
Src***
source
P-WSubVal
Substitute value for ac-
tive power limitation out-
side of normal feed-in
operation during commu-
nication disturbance
User Manual
Value/range
Explanation
Off
Deactivated
On
Activated
0.017%/s to
100.000%/s
Off
Deactivated
On
Activated
100 % ... 120 %
90 % ... 120 %
0 % ... 100 %
PrioPwrRtPrioPwrRt
Prioritization of reactive power
PrioPwrAt
Prioritization of active power
CAN
Interface of the communication
unit
UART
Via SMA Net
0 kW to 550 kW
Sunny Central 500CP XT
0 kW to 700 kW
Sunny Central 630CP XT
0 kW to 792 kW
Sunny Central 720CP XT
0 kW to 836 kW
Sunny Central 760CP XT
0 kW to 880 kW
Sunny Central 800CP XT
0 kW to 935 kW
Sunny Central 850CP XT
0 kW to 990 kW
Sunny Central 900CP XT
0 kW to 1100 kW
Sunny Central 1000CP XT
11 Operating Data and Parameters
Default
value
Country-
specific
0.166%/s
Off
111%
110 %
20 %
PrioPwrRtPri-
oPwrRt
UART
550 kW
700 kW
792 kW
836 kW
880 kW
935 kW
990 kW
1,100 kW
SCCPXT-E7-BA-en-58