SMA SUNNY CENTRAL 500CP XT User Manual page 127

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
PF-PFStop**
Displacement power fac-
tor cos φ at characteristic
curve point 2
The lower limit is defined
by the parameter PFAb-
sMin.
PF-PFExtStop** Excitation of the dis-
placement power factor
cos φ at characteristic
curve point 2
PF-WStr**
Feed-in power in % at
characteristic curve
point 1
PF-WStop**
Feed-in power in % at
characteristic curve
point 2
PF-WLockIn-
Activation voltage of the
Vtg**
cos φ(P) characteristic
curve, in %, relative to
the nominal voltage
PF-WLock-
Deactivation voltage of
OutVtg**
the cos φ(P) characteris-
tic curve, in %, relative to
the nominal voltage
PF-WLockTm
Waiting time for activa-
tion or deactivation of
the cos φ(P) characteris-
tic curve
Q-VDif**
Definition of voltage vari-
ation leading to a
change in reactive
power
Q-VArGra**
Definition of the reactive
power setpoint change in
one voltage step
Q-VDifTm**
Time period for which a
voltage change must be
present before the reac-
tive power setpoint Q-
VArGra changes.
User Manual
Value/range
Explanation
0.5 ... 1
OvExt
Overexcited
UnExt
Underexcited
0 % ... 90 %
10 % ... 100 %
0 % ... 110 %
0 % ... 110 %
0 s to 100 s
0.1 % ... 10 %
The value refers to the nominal
voltage VRtg.
0 % ... 100 %
The value refers to the nominal
power Pmax.
0 s to 120 s
11 Operating Data and Parameters
Default
value
0.9
OvExt
0 %
100 %
0 %
0 %
2 s
1 %
1 %
1 s
SCCPXT-E7-BA-en-58
127